Our Largest Fan by Airflow: 2,25,000 m³/h for a Paint Line

2,25,000 CMH150 mmWC215 HPDouble inlet

A surface-coating company in Maharashtra came to us for the air-supply fan of its paint line: 2,25,000 m³/h of supply air against 150 mmWC static. It is the largest single fan by airflow we have delivered, and the top of the flow envelope we publish.

The Duty

A paint line lives on its air balance. The supply unit has to hold a steady volume into the booths as its filters load between changes, so the duty point must sit on the stable part of the fan curve, not at its edge.

The approved drawing states the duty in full: 2,25,000 m³/h at 150 mmWC static, air at 40 °C, on a site 560 m above sea level, rated at a density of 1.04 kg/m³ rather than the 1.2 kg/m³ of standard air. That correction is why altitude and temperature belong on every enquiry. The drawing also sets the noise: 85 dB (+3) at 1 m, inlet and outlet ducted.

What We Supplied

One double-inlet, double-width centrifugal fan with a backward-inclined impeller, belt-driven at 770 rpm by a 215 HP, 4-pole IE3 motor rated for VFD duty, the motor in our scope. The shaft runs in spherical roller bearings in plummer blocks, the casing is split so the impeller can come out without lifting the whole fan, and both inlets carry mesh guards. Fan and motor sit on one base frame on anti-vibration mounts: about 5,650 kg with the motor.

The rotor is dynamically balanced to ISO 21940 G2.5, vibration is held to ISO 14694 category BV-3, and the first critical speed is at least 1.4 times the running speed. Testing to IS 4894 is written into the approved drawing. The finish: shot-blasted and phosphated, two coats of zinc-rich primer and a RAL 9002 top coat.

The Relationship

The same company had placed fans with us before. This one, the largest, followed them.

Bring Us Your Duty

If your line needs supply or exhaust air at large volume, send us the duty or the GA drawing: flow, static, temperature and site elevation. We will tell you plainly whether it sits inside our envelope and how we would build it.

— Mihir Kulkarni, Director, Jitamitra Electro Engineering

Engineered for Every Application.

The fan itself

Before dispatch

The double-inlet fan in this case study, photographed at our works before dispatch.

Double-inlet centrifugal fan for a paint-line air-supply unit, with its belt guard, before dispatch
Drive side of the 2,25,000 m³/h fan: the 215 HP motor on the common base frame
Inlet side of the double-inlet fan, showing the inlet ring and the split casing
The 2,25,000 m³/h air-supply fan from the belt-guard side, at our works
Questions

Frequently asked

What is the largest fan, by airflow, that Jitamitra has delivered?

A single double-inlet centrifugal fan supplying 2,25,000 m³/h at 150 mmWC static to a paint line, belt-driven by a 215 HP motor. It sets the top of the flow envelope we publish.

Why use a double-inlet fan at this volume?

A double-inlet, double-width wheel draws air from both sides, so it moves far more air than a single-inlet wheel of the same diameter and speed. At 2,25,000 m³/h that keeps the fan's size and running speed practical.

Was the fan selected at standard air?

The duty was referred to standard air to read the fan curve, and the fan was rated at the site's real density: 1.04 kg/m³, for air at 40 °C on a site 560 m above sea level.

Ready to quote?

Send us the duty point. We'll quote in 3 to 5 working days.*

Flow, static, gas temperature, application — or attach a spec, GA drawing or a multi-fan schedule. Engineer to engineer.

Get a quote → Email the desk

ISO 9001:2015 quality system · performance-tested to IS 4894 / ISO 5801 / AMCA 210 method · witnessed FAT on request.

*For our standard range. ATEX and special projects need 5 to 7 working days.